D P L
XACLAKE SLX
SLX type flow indicator is mainly composed of target rod, swing part, spring adjustment mechanism, travel switch and indication part. When the flow indicator annunciator is assembled, the target is placed in the middle of the pipeline and perpendicular to the water flow direction. When the water flows through the target (the flow is greater than the action flow value set by the annunciator), the pressure difference of the fluid speed makes the swing rod overcome the pre compression force of one spring and rotate and tilt relative to the rotation center. The upper end of the rod pushes the travel switch to act and send a normal signal until the target rod is limited, The pointer now points to the on position. When the water flow in the pipeline decreases gradually, the liquid flow differential pressure also decreases gradually. Under the action of spring force, the swing rod returns and looses the travel switch to send out the bottom flow signal. At this time, the pointer points to the closed position.
Main technical parameters
1. The medium pressure is 0.2-1mpa, and the filtered non corrosive liquid.
2. The ambient temperature is 0.5-40 ℃ and the relative humidity is less than 95%.
3. Rated voltage of signal switch: dc220v, 3A; AC220V、5A
4. It is installed indoors without explosive corrosion metal and damaged gas or dust on the X edge
5. Users can adjust the flow action value within a certain range.
6. The length of inlet and outlet pipelines shall be 5-10 times of the pipe diameter, and the straight pipe section shall be installed horizontally.
Selection example
Product Name: current indicator
Model: slx-25z slx-25zs
Note: "25" indicates pipe diameter, "Z" indicates unidirectional, "ZS" indicates bidirectional
Use and maintenance
1. Before using the annunciator, check whether the installation is correct and whether all fasteners are loose, and then try several times. It can be put into use without jamming and shaking.
2. The annunciator shall not be used on the pipeline lower than the "applicable flow" value, so as to avoid the impact of annunciator jitter on its service life.
3. Under normal working conditions, the annunciator does not need daily maintenance, but it can be checked every 2-3 years, mainly to check whether the rubber bushing has leakage and stroke
Whether the switch is reliable, etc. if it is damaged, it must be replaced.
4. Before installation, the product should be stored in a dry room with a temperature of 5-40 ℃ and no corrosive gas.
summary
Slx-z flow indicator, also known as flow control switch, is used to monitor the liquid flow in the pipeline. Connect the flow indicator in series in the pipeline. When there is normal flow liquid passing through the pipeline, the flow indicator sends a normal signal. When the liquid flow in the pipeline is lower than a certain value, it can automatically send out signals or alarms to protect the main equipment.
On the basis of retaining the x-point of SLX and 201 series flow indicators used by the original users, our company has further developed a new generation of new series products with intuitive flow display function and can work under any liquid medium conditions. It integrates the flow display and alarm function in the pipe, which has the characteristics of more intuition, higher degree of automation and wider scope of application.
characteristic
Free from environmental restrictions and vibration interference.
The lever and bearing mechanism are outside the medium and are not afraid of pollution.
There is a pointer and dial to directly display the fluid flow in the pipe.
It has dual control function, which can be used not only for x large and X small flow control, but also for alarm flow and shutdown flow control, but also for two-way (positive and negative) display.
The fully sealed structure is adopted to separate the bellows cavity of the flow indicator from the fluid medium by X, which can avoid the failure of target rod action caused by impurities entering the bellows, and can work normally under any adverse conditions such as abundant sediment and plankton.
All other parts of this product are made of stainless material.
technical parameter
Liquid medium in tube
Pressure: ≤ 1.0MPa
Liquid flow direction: unidirectional and bidirectional
Relative humidity: ≤ 95rh
Ambient temperature: ≤ 60 ℃
Contact capacity: AC220V, 3A; DC220V、0.5A